64
DX SERIES
TEMPERATURE CONTROLLER
TEMPERATURECONTROLLER
3
      

anddeterminesbytheamountofchangewhetherLBA
istobeONorOFF.
Whenthestatusata100%PIDcomputedvalue
continuesbeyondtheLBAsettingtime,theLBA
turnsONifthemeasured-value(PV)doesnotrise
by2℃(℉)ormore.
(Indirectaction,theabovealarmturnsONifthe
measured-valuedoesnotfallby2℃(℉)ormore.
Whenthestatusat0%PIDcomputedvalue
continuesbeyondtheLBAsettingtime,theLBA
turnsONifthemeasured-value(PV)doesnotfall
by2℃(℉)ormore.
(Indirectaction,theabovealarmturnsONifthe
measured-valuedoesnotriseby2℃(℉)ormore.)























-199to1770℃(℉)or
-199.9to999.9℃(℉)
1to7200sec.
(Settingbelow“0”cannotbemade)
1to3600sec.
(DactionturnsOFFwithDsetto“0”)
1to3600sec.
(IactionturnsOFFwithIsetto“0”)
1tospan℃(℉)or0.1tospan℃(℉)
(1 actionturnsOFFwiththisactionsetto“0”)
1tospan℃(℉)or0.1tospan℃(℉)
(ON/OFFactionwithPsetto“0”or“0.0”)
-199to1770℃(℉)or
-199.9to999.9℃(℉)
Min.toMax.scalepointInstrument.
0.1to100.0℃(℉)or1to100℃(℉)
1to100sec.
Min.toMax.scalepointInstrument.
0000:Nosetdatalocked.
0001:Onlytheset-value(SV)is
changeablewiththesetdatalocked.
0010/0011:Setdatalocked.

Usuallysettheset-valueoftheLBAtoavalueof
twicetheintegraltime(I).
TheLBAcanalsobesetbytheauto-tuning(AT)
function.Inthiscase,theset-valueisautomaticallyset
toavalueoftwicetheintegraltime(I).

LBAfunctionstartstomeasuretimefromthemoment
thatthePIDComputedValue(OutputONtime/cycle)
become0%or100%,anddetectstheamountof
ProcessValuechangeateachLBAsettingtime,



TheLBAisactivatedunderthefollowingconditions.
Controlled object trouble
....
Heater break, no power
supply,incorrectwiring,etc.
② Sensortrouble
....
Sensordisconnected,shorted,etc.
Actuator trouble
....
Burnt relay contact, incorrect wiring,
relaycontactnotclosed,etc.
Output circuit trouble
....
Burnt internal relay contact,
relaycontactnotopenorclosed,etc.
Input circuit trouble
....
The measured-value does not
changeevenifinputchanges,etc.
* If causes of the above trouble cannot be identified,
checkthecontrolsystem.

TheLBAfunctionisactivatedonlyatthe0%or100%
PIDcomputedvalue.
Therefore, the time from trouble occurrence till the
activationoftheLBAfunctionequalsthetimeuntilPID
computed value becomes 0% or 100% plus the LBA
settingtime.
The LBA function is activated while the auto-tuning
(AT)functionisactivated.
The LBA function is influenced by disturbances (heat
sources,etc.)andasaresultmaybeactivatedevenif
thereisnotroubleinthecontrolsystem.
IfLBAsettingtimeistooshortordoesnotmatchthe
controlledobject,theabovealarmmaynotbeturned
ONandOFFornotbeturnedON.Insuchacase,set
thesettingofLBAtobeslightlylonger.